400G DR4 vs FR4 vs LR4: which one to choose

Short answer: pick DR4 when you have parallel single-mode fiber, links up to 500 m and want to break 400G out to four 100G ports. Pick FR4 when you only have a duplex LC pair and the link is up to 2 km. Pick LR4 for one duplex pair up to 10 km. Beyond 10 km, ER4 covers 40 km. The fiber you already have usually decides before the distance does.

WincoTek Insights · 20 November 2026 · 5 min read

400G single-mode options at a glance (values from the WincoTek transceivers table and model pages)

TypeWincoTek modelReachFiber / connectorOptics4×100G breakoutMax. power
DR4 (QSFP-DD)WTQD400-DR4500 mParallel SMF, MPO-12 APC4 lanes, 1304.5–1317.5 nmYes, 4 × 100G DR8 W (datasheet target)
DR4 (QSFP112)WTQ112400-DR4-500C500 mParallel SMF, MPO-12 APC4 lanes, 1310 nm; host FEC requiredNot stated; ask us<12 W
FR4WTQD400-FR42 kmDuplex SMF, LC4 lanes at 1310 nm on one pairNo<12 W
LR4WTQD400-LR410 kmDuplex SMF, LC4 LAN-WDM lanes on one pairNo<12 W
4×LR1WTQD400-DR4-1010 kmParallel SMF, MPO-12 APC4 parallel lanesYes, 4 × 100G<8 W
ER4WTQD400-ER440 kmDuplex SMF, LC4 LAN-WDM lanes, EMLNo12 W max.

The difference in one sentence

All three carry 400G as four optical lanes of about 100G each. DR4 sends the four lanes side by side on four separate fibers in each direction. FR4 and LR4 put the four lanes on four different wavelengths and multiplex them onto a single fiber in each direction. Everything else, from connector to breakout to reach, follows from that design choice.

Start from the fiber you already have

Before comparing datasheets, look at the patch field. Parallel optics need parallel fiber: a DR4 port uses an MPO-12 connector with eight working fibers, four transmitting and four receiving. Wavelength-multiplexed optics need only one duplex LC pair. If your racks are already cabled with MPO trunks and cassettes, DR4 slots straight in. If the building, campus or metro route offers duplex pairs only, FR4 or LR4 is the realistic choice, because re-cabling for parallel fiber over hundreds of meters costs more than the optics you save.

The fiber type matters too. All the options in the table run on single-mode fiber. For multimode halls, 400G SR8 and SR4 types are the equivalents, with reach measured in tens of meters rather than kilometers.

When DR4 is the better answer

DR4 is built for the inside of a data center. In a leaf-spine fabric every leaf connects to every spine, so the number of uplinks, and of optics, grows quickly with each switch you add. A DR4 port can run as one 400G link or break out into four 100G DR links, each on its own fiber pair through an MPO-to-duplex-LC breakout cable. That lets a 400G spine port serve four 100G leaf or server ports, which keeps the spine port count and the number of switches down while you migrate.

Two things to check before ordering. First, the MPO connector on WincoTek DR4 modules is angle-polished (APC). An APC end face does not mate correctly with a flat PC one, so trunks, cassettes and breakout cords must have APC ends. Second, MPO links have to match on pin type (male on one side, female on the other) and on polarity; confirm both for the whole channel, not cord by cord.

The QSFP112 DR4 uses the same four 1310 nm lanes on MPO-12 APC, but plugs into a QSFP112 port with four 100G-class electrical lanes. The QSFP-DD DR4 uses an eight-lane 400GAUI-8 host interface. Check which port your switch has: the optical side of both is the same 400G DR4 class, the host side is not.

When FR4 or LR4 is the better answer

FR4 and LR4 trade breakout for fiber efficiency. One duplex LC pair carries the full 400G, which is what you want between buildings, between halls on different floors, or anywhere the number of available fibers is limited. FR4 covers up to 2 km, which is enough for most campus and large-site links. LR4 stretches to 10 km on the same single pair and suits data center interconnect inside a city district or between nearby sites.

Neither breaks out to 100G. If you need both 10 km reach and breakout, the 4×LR1 type (WTQD400-DR4-10) does that over parallel MPO-12 APC fiber. If you need more than 10 km on one pair, the ER4 reaches 40 km, but its receiver has a low ceiling: on short spans it needs an attenuator.

Check the link budget, not only the distance

Rated reach assumes typical fiber and connector losses. Real links have patch panels, splices and repairs. The safe method is simple:

  • Add the losses on the path: fiber attenuation, every connector and every splice.
  • Keep at least 3 dB of margin for bends, repairs and ageing.
  • If the link is already built, measure it: a light source at one end, a power meter at the other; the loss is the difference between the two readings.
  • Check both directions: transmitter power minus link loss and margin must land between the receiver sensitivity and the maximum receive power in the datasheet.

A short FR4 link with many patch panels can be harder to close than a clean 2 km run. An LR4 link at 8 km through two buildings and several splices may need more care than its 10 km rating suggests. Do the sum before choosing the optic, and use the datasheet minimum values, not typical ones.

Power and the host port

Power is listed in the table because host ports have power classes. The QSFP-DD FR4 and LR4 are rated under 12 W, the QSFP-DD DR4 at 8 W (a target value in its datasheet), the QSFP112 DR4 under 12 W and the ER4 at 12 W maximum. Make sure the switch line card supports the module power class in every port you plan to fill, and keep high-power modules spread across the faceplate where the platform allows it.

Both ends must match

A link works only between compatible optics: DR4 to DR4 (or to four 100G DR ports in breakout), FR4 to FR4, LR4 to LR4. Mixing FR4 at one end with LR4 at the other is not a supported design, even though both use duplex LC. Order the same type for both ends, coded for each host platform, and test coded samples on your equipment before a volume order.

Quick decision list

  • MPO trunks in place, up to 500 m, want 4×100G breakout: DR4.
  • Duplex LC pair only, up to 2 km: FR4.
  • Duplex LC pair only, up to 10 km: LR4.
  • Parallel fiber, up to 10 km, breakout needed: 4×LR1.
  • Duplex pair, up to 40 km: ER4, with an attenuator on short spans.

Not sure which applies? Send us the host model, the fiber type and connector in your patch field and the link length or measured loss, and we will match the optic and a sample plan.

Plan it with us.

Send your requirements and we reply with a matched design, part numbers and a sample or proposal plan.